Machine Model: REGC_B
Following checks and corrections are applied during Validation and AutoCorrection.
- If Tfltr < 4*TimeStep then Tfltr will use 0.0
- If Tg < 4*TimeStep then Tg will use 4*TimeStep, and if Tg > 0.2 then Tg = 0.2
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Tfltr | Voltage sensor time constant |
| Tg | Ip and Iq command time constant, seconds |
| Te | Generator network impedance time constant, seconds |
| rrpwr | LVPL ramprate limit, p.u. |
| Re | Generator effective resistance, p.u. |
| Xe | Generator effective reactive, p.u. |
| Iqrmax | Reactive current recovery positive rate limit (set to zero or negative value to disable) |
| Iqrmin | Reactive current recovery negative rate limit (set to zero or positive value to disable) |
| Rateflag | RateFlag; 0 means active current ramp rate, otherwise active power ramp rate |
| Imax | Maximum curring rating of the converter, p.u. |
| DQFlag | PQ priority Flag; 0 = Q priority, otherwise P priority |